Knob and tube wiring is usually found in homes built about 50 years ago that have not had the wiring updated. Knob and tube wiring gets its name from the insulator knobs used to keep the wires isolated from objects and the ceramic tubes used to line holes through wooden floor joists. You may find it with older 60 amp services.

Although the actual wire used may be no different from that used today for the most part, it consists of only a hot (black) and neutral (white) wire with no ground wire. Both wires must run separately to fixtures as opposed to those used now which are contained within one plastic sheathing.

Knob and tube wiring can be safe and functional. Hire a qualified electrician to inspect the wiring to determine its safety. With proper documentation from a certified electrician many insurance companies will readily insure your home. While I have safely owned many homes with knob and tube, there are some issues to be concerned about, such as, the fact that there is no ground wire, which may be an issue for today’s lifestyle, high electricity usage and technology. Also, there are potential fire hazards with the break down of the insulation around the knob and tube wiring that comes with age, and should the black and white wires make contact.

In recent years some home insurance companies have begun to refuse to insure homes with knob and tube wiring, however, there are companies that continue to offer regular priced policies for homes with knob and tube, and others who ask a premium for this insurance. If you have any qualms about the safety of your knob and tube wiring, you can hire an electrician to update your home wiring. Be sure to get a quote, and expect to pay more to update a two- or three-story home, than you would for a bungalow. Keep the receipt to show prospective buyers when it comes time to sell.

If you intend to purchase a home in an area where knob and tube wiring was used then ask your realtor for advice on securing insurance and peace of mind. Your realtor may recommend the use of a condition in your offer to purchase that allows you the buyer to satisfy yourself that the house is insurable. That way you won’t be stuck struggling to find insurance right before closing.
 

Electrical Dangers in Homes With Knob and Tube Wiring

by Brian Cook, May 2007
 
Based on about 100 home electrical safety surveys that I have conducted done over the past 6 months, I have found only one home with dangerous knob and tube cabling. In this house the hazardous knob-and-tube wiring was a direct result of over fusing which resulted in over-loading of the conductors followed by insulation breakdown. With this home I rated the home high risk and presented that the home be rewired. The homeowner has done so.
 

A common danger relating to knob and tube wiring is the use of electrical devices requiring grounding that are connected to "ungrounded, 3-prong receptacles" (found in virtually all homes examined). This situation, the "lack of ground" can easily be remedied with the replacement of the ungrounded 3-prong receptacles with GFCI receptacles (or GFCI protection at the panel). This is an excellent solution that in my opinion provides equal if not better ground protection than standard 3-prong grounded receptacles.

A second danger relating to knob and tube wiring is the implementation of "Handyman add-ons". These add-ons are often found, though not exclusively, tapped into existing knob and tube circuits. Handyman add-ons can be very dangerous, consisting of, for example undersized wire, open splices, poor connections and/or dangerous placement or type of device to which it is powering. My findings show that dangerous "Handyman add-ons" are not limited to homes with knob and tube wiring, but related to the age of the house. Regarding homes with serious electrical hazards, I have found a particularly high incidence in homes with secondary suites, a result of the homeowners doing the wiring themselves or by unlicensed electricians.
 
Interestingly, in all homes examined, I have conducted "voltage drop test under loading", an excellent test to determine the conductivity of the conductors, thus a presentation of electrical heat dissipated in the conductors and connections enroute. Any poor connections clearly show up whether the cabling be knob-and-tube, aluminum, or modern wiring. Poor electrical connections can lead to arcing followed by fire. My findings show that if there has not been "handyman tampering" the conductivity of knob-and tube circuits has been by-in-large superior to that modern cabling (1). This is likely due to the soldered connections and the shorter wire runs of knob and tube wiring.
 
A final mention: Of significant concern is dangers of service supply conductors (home powerline). The two very dangerous concerns that have found have been (a) broken "Emily knob" (in 3% of homes) and (b) trees applying pressure to service-supply conductors (in 26% of homes), causing tension on the conductors which could lead to a broken Emily knob. Once the Emily knob has detached from the house, the service supply conductors are at high risk of becoming detached at a point close to the side of the house. This can, and has led to fire outbreak.
 

In summary, electrical hazards have been found both in homes with and without knob and tube wiring, but the hazards have by-in large not been related to the knob and tube wiring itself. Homes with significant hazards have by-in-large been related to (a) the age of the house (the number of years where Handyman tampering could have occurred), (b) the application of the house (secondary suite or not), and proximity of trees to the service supply conductors. A comprehensive electrical inspection by qualified personnel is the only sure way to identify if and where there are electrical hazards.

 
Brian Cook
BCTQ Electrician, Field Safety Representative (Electrical) and owner PowerCheck
 
1. Voltage drop test under loading: Canadian Electrical Code states that at full load values within 5% are acceptable. Modern home wiring circuits typically show values in range of 4 to 4.5 %; Knob & tube circuits most often measure values in the range of 1 to 2%; On aluminum wiring circuits I have measured values exceeding 10%. This additional voltage drop is likely due one or more poor connections enroute to the receptacle, and must be repaired. A 1500 watt load (e.g. an electric kettle) connected to a circuit with a 5% voltage drop at a poor connection yields 60 watts heat generated at that connection. This would be comparable to the heat generated from a 60 W light bulb; most dangerous and must be repaired.
 

 
 
Read
Categories:   2008 vancouver | 2009 Budget | 2009 market | 2009 Real Estate Market | 2010 real estate market | animation | banning | BC Property Assessments | BC Property Transfer Tax | BC; British Columbia | Best Real Estate Agent | book illustrator | Brentwood Park | Brentwood Park, Burnaby North | Brentwood Park, Burnaby North Real Estate | Burnaby East Real Estate | Burnaby North | Burnaby North Real Estate | Burnaby South | Burnaby South Real Estate | buy | buyer | Buyers | buying | canadian real estate market | Capitol Hill BN | Capitol Hill BN, Burnaby North Real Estate | cell phones | Central Pt Coquitlam, Port Coquitlam Real Estate | childrens books | Chilliwack | Class of the Titans | Clayton, Cloverdale | Coal Harbour, Vancouver West Real Estate | Collingwood VE | Collingwood VE, Vancouver East | Collingwood VE, Vancouver East Real Estate | condos | Consumer Savings | Coquitlam West, Coquitlam Real Estate | Deer Lake | Deer Lake Place | Deer Lake Place, Burnaby South | Deer Lake Place, Burnaby South Real Estate | Deer Lake, Burnaby South | Deer Lake, Burnaby South Real Estate | Downtown NW, New Westminster Real Estate | Downtown VE | Downtown VE, Vancouver East | Downtown VE, Vancouver East Real Estate | Downtown VW | Downtown VW, Vancouver West | Downtown VW, Vancouver West Real Estate | Downtown, Vancouver West Real Estate | driving | Dunbar, Vancouver West Real Estate | east side condos | eco-friendly | Edmonds BE | Edmonds BE, Burnaby East Real Estate | electrical | Fairview VW, Vancouver West Real Estate | False Creek, Vancouver West Real Estate | FINTRAC | first | First-time buyers | Fraser VE, Vancouver East Real Estate | Fraserview VE | Fraserview VE, Vancouver East | Fraserview VE, Vancouver East Real Estate | Fraserview, Vancouver East Real Estate | free reports | FSBO | George of the Jungle | Georgia Straight | GlenBrooke North, New Westminster Real Estate | Government Road, Burnaby North Real Estate | Grandview VE | Grandview VE, Vancouver East | Grandview VE, Vancouver East Real Estate | Grandview Woodland, Vancouver East Real Estate | grants | green | Hamilton, North Vancouver Real Estate | Hastings | Hastings East | Hastings East, Vancouver East | Hastings East, Vancouver East Real Estate | Hastings Sunrise, Vancouver East Real Estate | Hastings, Vancouver East | Hastings, Vancouver East Real Estate | Highgate, Burnaby South Real Estate | Home Inspections | Home owners | home renovations | Homeowners | houses | Housing | housing costs | housing forecast | HST | insulation | Killarney VE, Vancouver East Real Estate | Kip and Zara | Kitsilano | Kitsilano, Vancouver West | Kitsilano, Vancouver West Real Estate | Knob and Tube Wiring | Laura Stein | law | listings | Lyn Hart | Macdonald Realty | Macdonald Realty Ltd. | Main Street | Main, Vancouver East Real Estate | mar | market | market value | Meadow Brook, Coquitlam Real Estate | Mercer Report | Metrotown, Burnaby South Real Estate | Montecito, Burnaby North Real Estate | mor | mort | mortgage rates | mortgage rules | Mount Pleasant VE | Mount Pleasant VE, Vancouver East | Mount Pleasant VE, Vancouver East Real Estate | Mount Pleasant VW | Mount Pleasant VW, Vancouver West | Mount Pleasant VW, Vancouver West Real Estate | New Listings | New Westminster | New Westminster Real Estate | non resident buying and selling | North Shore Pt Moody, Port Moody Real Estate | Northlands, North Vancouver Real Estate | old houses | Open houses | outlook | Port Moody Centre, Port Moody Real Estate | Property Transfer Tax | public opens | Pucca | quality of living | Quay, New Westminster Real Estate | Queensborough, New Westminster Real Estate | quick sale | real | real estate | Real Estate Fees | real estate investors | real estate market | real estate market predictions | real estate market report | rebates | Renfrew VE | Renfrew VE, Vancouver East Real Estate | reports | Roche Point, North Vancouver Real Estate | sales | Sapperton | Sapperton, New Westminster | sel | sell | seller | sellers | selling your home | selling, home staging, real estate, interior design | Silver Valley, Maple Ridge Real Estate | South Marine, Vancouver East Real Estate | South Slope | South Slope, Burnaby South | South Slope, Burnaby South Real Estate | statistics | Studio B | Tax Credit | telemarketing | telephone soliciting | texting | Uptown NW | Uptown NW, New Westminster | Uptown NW, New Westminster Real Estate | vanc | Vancouver | vancouver condos | Vancouver East | Vancouver East Real Estate | Vancouver Heights, Burnaby North Real Estate | Vancouver Real Estate blog | Vancouver real estate market | Vancouver West | Vancouver West Real Estate | Victoria VE, Vancouver East Real Estate | West End NW, New Westminster Real Estate | West End VW | West End VW, Vancouver West | West End VW, Vancouver West Real Estate | Whalley, North Surrey Real Estate | Yaletown, Vancouver West Real Estate
Reciprocity Logo The data relating to real estate on this website comes in part from the MLS® Reciprocity program of either the Greater Vancouver REALTORS® (GVR), the Fraser Valley Real Estate Board (FVREB) or the Chilliwack and District Real Estate Board (CADREB). Real estate listings held by participating real estate firms are marked with the MLS® logo and detailed information about the listing includes the name of the listing agent. This representation is based in whole or part on data generated by either the GVR, the FVREB or the CADREB which assumes no responsibility for its accuracy. The materials contained on this page may not be reproduced without the express written consent of either the GVR, the FVREB or the CADREB.